Filtered by vendor Siemens
Subscriptions
Total
2117 CVE
CVE | Vendors | Products | Updated | CVSS v3.1 |
---|---|---|---|---|
CVE-2017-6870 | 1 Siemens | 1 Simatic Wincc Sm\@rtclient | 2025-04-20 | N/A |
A vulnerability was discovered in Siemens SIMATIC WinCC Sm@rtClient for Android (All versions before V1.0.2.2). The existing TLS protocol implementation could allow an attacker to read and modify data within a TLS session while performing a Man-in-the-Middle (MitM) attack. | ||||
CVE-2017-14023 | 1 Siemens | 2 Simatic Pcs7, Simatic Wincc | 2025-04-20 | 4.9 Medium |
An Improper Input Validation issue was discovered in Siemens SIMATIC PCS 7 V8.1 prior to V8.1 SP1 with WinCC V7.3 Upd 13, and V8.2 all versions. The improper input validation vulnerability has been identified, which may allow an authenticated remote attacker who is a member of the administrators group to crash services by sending specially crafted messages to the DCOM interface. | ||||
CVE-2017-6868 | 1 Siemens | 1 Simatic Cp 44x-1 Redundant Network Access Modules | 2025-04-20 | N/A |
An Improper Authentication issue was discovered in Siemens SIMATIC CP 44x-1 RNA, all versions prior to 1.4.1. An unauthenticated remote attacker may be able to perform administrative actions on the Communication Process (CP) of the RNA series module, if network access to Port 102/TCP is available and the configuration file for the CP is stored on the RNA's CPU. | ||||
CVE-2017-6867 | 1 Siemens | 3 Simatic Wincc, Simatic Wincc \(tia Portal\), Simatic Wincc Runtime | 2025-04-20 | N/A |
A vulnerability was discovered in Siemens SIMATIC WinCC (V7.3 before Upd 11 and V7.4 before SP1), SIMATIC WinCC Runtime Professional (V13 before SP2 and V14 before SP1), SIMATIC WinCC (TIA Portal) Professional (V13 before SP2 and V14 before SP1) that could allow an authenticated, remote attacker who is member of the "administrators" group to crash services by sending specially crafted messages to the DCOM interface. | ||||
CVE-2015-7705 | 4 Citrix, Netapp, Ntp and 1 more | 10 Xenserver, Clustered Data Ontap, Data Ontap and 7 more | 2025-04-20 | 9.8 Critical |
The rate limiting feature in NTP 4.x before 4.2.8p4 and 4.3.x before 4.3.77 allows remote attackers to have unspecified impact via a large number of crafted requests. | ||||
CVE-2017-6866 | 1 Siemens | 1 Xhq Server | 2025-04-20 | N/A |
A vulnerability was discovered in Siemens XHQ server 4 and 5 (4 before V4.7.1.3 and 5 before V5.0.0.2) that could allow an authenticated low-privileged remote user to gain read access to data in the XHQ solution exceeding his configured permission level. | ||||
CVE-2017-6864 | 1 Siemens | 1 Ruggedcom Rox I | 2025-04-20 | N/A |
The integrated web server in Siemens RUGGEDCOM ROX I (all versions) at port 10000/TCP could allow an authenticated user to perform stored Cross-Site Scripting attacks. | ||||
CVE-2015-7855 | 4 Debian, Netapp, Ntp and 1 more | 11 Debian Linux, Clustered Data Ontap, Data Ontap and 8 more | 2025-04-20 | 6.5 Medium |
The decodenetnum function in ntpd in NTP 4.2.x before 4.2.8p4, and 4.3.x before 4.3.77 allows remote attackers to cause a denial of service (assertion failure) via a 6 or mode 7 packet containing a long data value. | ||||
CVE-2017-9944 | 1 Siemens | 2 7kt Pac1200 Data Manager, 7kt Pac1200 Data Manager Firmware | 2025-04-20 | N/A |
A vulnerability has been identified in Siemens 7KT PAC1200 data manager (7KT1260) in all versions < V2.03. The integrated web server (port 80/tcp) of the affected devices could allow an unauthenticated remote attacker to perform administrative operations over the network. | ||||
CVE-2015-7973 | 5 Canonical, Freebsd, Netapp and 2 more | 9 Ubuntu Linux, Freebsd, Clustered Data Ontap and 6 more | 2025-04-20 | 6.5 Medium |
NTP before 4.2.8p6 and 4.3.x before 4.3.90, when configured in broadcast mode, allows man-in-the-middle attackers to conduct replay attacks by sniffing the network. | ||||
CVE-2017-2685 | 1 Siemens | 3 Sinumerik Integrate Access Mymachine\/ethernet, Sinumerik Integrate Operate Client, Sinumerik Operate | 2025-04-20 | N/A |
Siemens SINUMERIK Integrate Operate Clients between 2.0.3.00.016 (including) and 2.0.6 (excluding) and between 3.0.4.00.032 (including) and 3.0.6 (excluding) contain a vulnerability that could allow an attacker to read and manipulate data in TLS sessions while performing a man-in-the-middle (MITM) attack. | ||||
CVE-2017-2684 | 1 Siemens | 1 Simatic Logon | 2025-04-20 | N/A |
Siemens SIMATIC Logon prior to V1.5 SP3 Update 2 could allow an attacker with knowledge of a valid user name, and physical or network access to the affected system, to bypass the application-level authentication. | ||||
CVE-2017-2689 | 1 Siemens | 1 Ruggedcom Rox I | 2025-04-20 | N/A |
Siemens RUGGEDCOM ROX I (all versions) allow an authenticated user to bypass access restrictions in the web interface at port 10000/TCP to obtain privileged file system access or change configuration settings. | ||||
CVE-2017-2688 | 1 Siemens | 1 Ruggedcom Rox I | 2025-04-20 | N/A |
The integrated web server in Siemens RUGGEDCOM ROX I (all versions) at port 10000/TCP could allow remote attackers to perform actions with the privileges of an authenticated user, provided the targeted user has an active session and is induced into clicking on a malicious link or into visiting a malicious website, aka CSRF. | ||||
CVE-2017-2687 | 1 Siemens | 1 Ruggedcom Rox I | 2025-04-20 | N/A |
Siemens RUGGEDCOM ROX I (all versions) contain a vulnerability in the integrated web server at port 10000/TCP which is prone to reflected Cross-Site Scripting attacks if an unsuspecting user is induced to click on a malicious link. | ||||
CVE-2017-2686 | 1 Siemens | 1 Ruggedcom Rox I | 2025-04-20 | N/A |
Siemens RUGGEDCOM ROX I (all versions) contain a vulnerability that could allow an authenticated user to read arbitrary files through the web interface at port 10000/TCP and access sensitive information. | ||||
CVE-2017-2683 | 1 Siemens | 1 Ruggedcom Network Management Software | 2025-04-20 | N/A |
A non-privileged user of the Siemens web application RUGGEDCOM NMS < V1.2 on port 8080/TCP and 8081/TCP could perform a persistent Cross-Site Scripting (XSS) attack, potentially resulting in obtaining administrative permissions. | ||||
CVE-2017-2682 | 1 Siemens | 1 Ruggedcom Network Management Software | 2025-04-20 | N/A |
The Siemens web application RUGGEDCOM NMS < V1.2 on port 8080/TCP and 8081/TCP could allow a remote attacker to perform a Cross-Site Request Forgery (CSRF) attack, potentially allowing an attacker to execute administrative operations, provided the targeted user has an active session and is induced to trigger a malicious request. | ||||
CVE-2017-2681 | 1 Siemens | 155 Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware, Ek-ertec 200 Pn Io and 152 more | 2025-04-20 | 6.5 Medium |
Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected. | ||||
CVE-2017-2680 | 1 Siemens | 183 S110 Pn, Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware and 180 more | 2025-04-20 | 6.5 Medium |
Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected. |