Filtered by vendor Siemens
Subscriptions
Total
1936 CVE
CVE | Vendors | Products | Updated | CVSS v3.1 |
---|---|---|---|---|
CVE-2017-9944 | 1 Siemens | 2 7kt Pac1200 Data Manager, 7kt Pac1200 Data Manager Firmware | 2025-04-20 | N/A |
A vulnerability has been identified in Siemens 7KT PAC1200 data manager (7KT1260) in all versions < V2.03. The integrated web server (port 80/tcp) of the affected devices could allow an unauthenticated remote attacker to perform administrative operations over the network. | ||||
CVE-2017-9945 | 1 Siemens | 2 7km Pac Switched Ethernet Profinet Expansion Module, 7km Pac Switched Ethernet Profinet Expansion Module Firmware | 2025-04-20 | N/A |
In the Siemens 7KM PAC Switched Ethernet PROFINET expansion module (All versions < V2.1.3), a Denial-of-Service condition could be induced by a specially crafted PROFINET DCP packet sent as a local Ethernet (Layer 2) broadcast. The affected component requires a manual restart via the main device to recover. | ||||
CVE-2017-9946 | 1 Siemens | 8 Apogee Pxc, Apogee Pxc Firmware, Apogee Pxc Modular and 5 more | 2025-04-20 | 7.5 High |
A vulnerability has been identified in Siemens APOGEE PXC and TALON TC BACnet Automation Controllers in all versions <V3.5. An attacker with network access to the integrated web server (80/tcp and 443/tcp) could bypass the authentication and download sensitive information from the device. | ||||
CVE-2017-9947 | 1 Siemens | 8 Apogee Pxc, Apogee Pxc Firmware, Apogee Pxc Modular and 5 more | 2025-04-20 | 5.3 Medium |
A vulnerability has been identified in Siemens APOGEE PXC and TALON TC BACnet Automation Controllers in all versions <V3.5. A directory traversal vulnerability could allow a remote attacker with network access to the integrated web server (80/tcp and 443/tcp) to obtain information on the structure of the file system of the affected devices. | ||||
CVE-2017-6864 | 1 Siemens | 1 Ruggedcom Rox I | 2025-04-20 | N/A |
The integrated web server in Siemens RUGGEDCOM ROX I (all versions) at port 10000/TCP could allow an authenticated user to perform stored Cross-Site Scripting attacks. | ||||
CVE-2017-6865 | 1 Siemens | 16 Pcs 7, Primary Setup Tool, Security Configuration Tool and 13 more | 2025-04-20 | N/A |
A vulnerability has been identified in Primary Setup Tool (PST) (All versions < V4.2 HF1), SIMATIC Automation Tool (All versions < V3.0), SIMATIC NET PC-Software (All versions < V14 SP1), SIMATIC PCS 7 V8.1 (All versions), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1), SIMATIC STEP 7 (TIA Portal) V13 (All versions < V13 SP2), SIMATIC STEP 7 (TIA Portal) V14 (All versions < V14 SP1), SIMATIC STEP 7 V5.X (All versions < V5.6), SIMATIC WinAC RTX 2010 SP2 (All versions), SIMATIC WinAC RTX F 2010 SP2 (All versions), SIMATIC WinCC (TIA Portal) V13 (All versions < V13 SP2), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1), SIMATIC WinCC V7.2 and prior (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Update 15), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd1), SIMATIC WinCC flexible 2008 (All versions < flexible 2008 SP5), SINAUT ST7CC (All versions installed in conjunction with SIMATIC WinCC < V7.3 Update 15), SINEMA Server (All versions < V14), SINUMERIK 808D Programming Tool (All versions < V4.7 SP4 HF2), SMART PC Access (All versions < V2.3), STEP 7 - Micro/WIN SMART (All versions < V2.3), Security Configuration Tool (SCT) (All versions < V5.0). Specially crafted PROFINET DCP broadcast packets sent to the affected products on a local Ethernet segment (Layer 2) could cause a Denial-of-Service condition of some services. The services require manual restart to recover. | ||||
CVE-2017-6866 | 1 Siemens | 1 Xhq Server | 2025-04-20 | N/A |
A vulnerability was discovered in Siemens XHQ server 4 and 5 (4 before V4.7.1.3 and 5 before V5.0.0.2) that could allow an authenticated low-privileged remote user to gain read access to data in the XHQ solution exceeding his configured permission level. | ||||
CVE-2017-6867 | 1 Siemens | 3 Simatic Wincc, Simatic Wincc \(tia Portal\), Simatic Wincc Runtime | 2025-04-20 | N/A |
A vulnerability was discovered in Siemens SIMATIC WinCC (V7.3 before Upd 11 and V7.4 before SP1), SIMATIC WinCC Runtime Professional (V13 before SP2 and V14 before SP1), SIMATIC WinCC (TIA Portal) Professional (V13 before SP2 and V14 before SP1) that could allow an authenticated, remote attacker who is member of the "administrators" group to crash services by sending specially crafted messages to the DCOM interface. | ||||
CVE-2017-6868 | 1 Siemens | 1 Simatic Cp 44x-1 Redundant Network Access Modules | 2025-04-20 | N/A |
An Improper Authentication issue was discovered in Siemens SIMATIC CP 44x-1 RNA, all versions prior to 1.4.1. An unauthenticated remote attacker may be able to perform administrative actions on the Communication Process (CP) of the RNA series module, if network access to Port 102/TCP is available and the configuration file for the CP is stored on the RNA's CPU. | ||||
CVE-2017-6869 | 1 Siemens | 1 Viewport For Web Office Portal | 2025-04-20 | N/A |
A vulnerability was discovered in Siemens ViewPort for Web Office Portal before revision number 1453 that could allow an unauthenticated remote user to upload arbitrary code and execute it with the permissions of the operating-system user running the web server by sending specially crafted network packets to port 443/TCP or port 80/TCP. | ||||
CVE-2017-6870 | 1 Siemens | 1 Simatic Wincc Sm\@rtclient | 2025-04-20 | N/A |
A vulnerability was discovered in Siemens SIMATIC WinCC Sm@rtClient for Android (All versions before V1.0.2.2). The existing TLS protocol implementation could allow an attacker to read and modify data within a TLS session while performing a Man-in-the-Middle (MitM) attack. | ||||
CVE-2017-6871 | 1 Siemens | 2 Simatic Wincc Sm\@rtclient, Simatic Wincc Sm\@rtclient Lite | 2025-04-20 | N/A |
A vulnerability was discovered in Siemens SIMATIC WinCC Sm@rtClient for Android (All versions before V1.0.2.2) and SIMATIC WinCC Sm@rtClient for Android Lite (All versions before V1.0.2.2). An attacker with physical access to an unlocked mobile device, that has the affected app running, could bypass the app's authentication mechanism under certain conditions. | ||||
CVE-2017-6872 | 1 Siemens | 4 Ozw672, Ozw672 Firmware, Ozw772 and 1 more | 2025-04-20 | N/A |
A vulnerability was discovered in Siemens OZW672 (all versions) and OZW772 (all versions) that could allow an attacker with access to port 21/tcp to access or alter historical measurement data stored on the device. | ||||
CVE-2017-6873 | 1 Siemens | 4 Ozw672, Ozw672 Firmware, Ozw772 and 1 more | 2025-04-20 | N/A |
A vulnerability was discovered in Siemens OZW672 (all versions) and OZW772 (all versions) that could allow an attacker to read and manipulate data in TLS sessions while performing a man-in-the-middle (MITM) attack on the integrated web server on port 443/tcp. | ||||
CVE-2017-6458 | 4 Apple, Hpe, Ntp and 1 more | 5 Mac Os X, Hpux-ntp, Ntp and 2 more | 2025-04-20 | 8.8 High |
Multiple buffer overflows in the ctl_put* functions in NTP before 4.2.8p10 and 4.3.x before 4.3.94 allow remote authenticated users to have unspecified impact via a long variable. | ||||
CVE-2017-5689 | 3 Hpe, Intel, Siemens | 71 Proliant Ml10 Gen9 Server, Proliant Ml10 Gen9 Server Firmware, Active Management Technology Firmware and 68 more | 2025-04-20 | 9.8 Critical |
An unprivileged network attacker could gain system privileges to provisioned Intel manageability SKUs: Intel Active Management Technology (AMT) and Intel Standard Manageability (ISM). An unprivileged local attacker could provision manageability features gaining unprivileged network or local system privileges on Intel manageability SKUs: Intel Active Management Technology (AMT), Intel Standard Manageability (ISM), and Intel Small Business Technology (SBT). | ||||
CVE-2017-5711 | 3 Asus, Intel, Siemens | 394 B150-a, B150-a Firmware, B150-plus and 391 more | 2025-04-20 | 7.8 High |
Multiple buffer overflows in Active Management Technology (AMT) in Intel Manageability Engine Firmware 8.x/9.x/10.x/11.0/11.5/11.6/11.7/11.10/11.20 allow attacker with local access to the system to execute arbitrary code with AMT execution privilege. | ||||
CVE-2017-5712 | 3 Asus, Intel, Siemens | 394 B150-a, B150-a Firmware, B150-plus and 391 more | 2025-04-20 | 7.2 High |
Buffer overflow in Active Management Technology (AMT) in Intel Manageability Engine Firmware 8.x/9.x/10.x/11.0/11.5/11.6/11.7/11.10/11.20 allows attacker with remote Admin access to the system to execute arbitrary code with AMT execution privilege. | ||||
CVE-2017-2680 | 1 Siemens | 183 S110 Pn, Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware and 180 more | 2025-04-20 | 6.5 Medium |
Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected. | ||||
CVE-2017-2681 | 1 Siemens | 155 Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware, Ek-ertec 200 Pn Io and 152 more | 2025-04-20 | 6.5 Medium |
Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected. |