Filtered by vendor Siemens
Subscriptions
Total
1940 CVE
CVE | Vendors | Products | Updated | CVSS v3.1 |
---|---|---|---|---|
CVE-2013-0700 | 1 Siemens | 18 Simatic S7-1200, Simatic S7-1200 Cpu 1211c, Simatic S7-1200 Cpu 1211c Firmware and 15 more | 2025-04-11 | N/A |
Siemens SIMATIC S7-1200 PLCs 2.x and 3.x allow remote attackers to cause a denial of service (defect-mode transition and control outage) via crafted packets to TCP port 102 (aka the ISO-TSAP port). | ||||
CVE-2013-0679 | 1 Siemens | 2 Simatic Pcs7, Wincc | 2025-04-11 | N/A |
Directory traversal vulnerability in the web server in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote authenticated users to read arbitrary files via vectors involving a query for a pathname. | ||||
CVE-2011-4532 | 1 Siemens | 1 Automation License Manager | 2025-04-11 | N/A |
Absolute path traversal vulnerability in the ALMListView.ALMListCtrl ActiveX control in almaxcx.dll in the graphical user interface in Siemens Automation License Manager (ALM) 2.0 through 5.1+SP1+Upd2 allows remote attackers to overwrite arbitrary files via the Save method. | ||||
CVE-2013-0678 | 1 Siemens | 2 Simatic Pcs7, Wincc | 2025-04-11 | N/A |
Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, does not properly represent WebNavigator credentials in a database, which makes it easier for remote authenticated users to obtain sensitive information via a SQL query. | ||||
CVE-2013-0677 | 1 Siemens | 2 Simatic Pcs7, Wincc | 2025-04-11 | N/A |
The web server in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote attackers to obtain sensitive information or cause a denial of service via a crafted project file. | ||||
CVE-2011-4531 | 1 Siemens | 1 Automation License Manager | 2025-04-11 | N/A |
Siemens Automation License Manager (ALM) 4.0 through 5.1+SP1+Upd1 allows remote attackers to cause a denial of service (NULL pointer dereference and daemon crash) via crafted content in a (1) get_target_ocx_param or (2) send_target_ocx_param command. | ||||
CVE-2013-0676 | 1 Siemens | 2 Simatic Pcs7, Wincc | 2025-04-11 | N/A |
Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, does not properly assign privileges for the database containing WebNavigator credentials, which allows remote authenticated users to obtain sensitive information via a SQL query. | ||||
CVE-2013-0675 | 1 Siemens | 2 Simatic Pcs7, Wincc | 2025-04-11 | N/A |
Buffer overflow in CCEServer (aka the central communications component) in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote attackers to cause a denial of service via a crafted packet. | ||||
CVE-2011-4530 | 1 Siemens | 1 Automation License Manager | 2025-04-11 | N/A |
Siemens Automation License Manager (ALM) 4.0 through 5.1+SP1+Upd1 does not properly copy fields obtained from clients, which allows remote attackers to cause a denial of service (exception and daemon crash) via long fields, as demonstrated by fields to the (1) open_session->workstation->NAME or (2) grant->VERSION function. | ||||
CVE-2013-0674 | 1 Siemens | 2 Simatic Pcs7, Wincc | 2025-04-11 | N/A |
Buffer overflow in the RegReader ActiveX control in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote attackers to execute arbitrary code via a long parameter. | ||||
CVE-2013-0672 | 1 Siemens | 1 Wincc Tia Portal | 2025-04-11 | N/A |
Cross-site scripting (XSS) vulnerability in the HMI web application in Siemens WinCC (TIA Portal) 11 allows remote authenticated users to inject arbitrary web script or HTML via unspecified data. | ||||
CVE-2011-4529 | 1 Siemens | 1 Automation License Manager | 2025-04-11 | N/A |
Multiple buffer overflows in Siemens Automation License Manager (ALM) 4.0 through 5.1+SP1+Upd1 allow remote attackers to execute arbitrary code via a long serialid field in an _licensekey command, as demonstrated by the (1) check_licensekey or (2) read_licensekey command. | ||||
CVE-2013-0671 | 1 Siemens | 1 Wincc Tia Portal | 2025-04-11 | N/A |
Directory traversal vulnerability in Siemens WinCC (TIA Portal) 11 allows remote authenticated users to read HMI web-application source code and user-defined scripts via a crafted URL. | ||||
CVE-2013-0670 | 1 Siemens | 1 Wincc Tia Portal | 2025-04-11 | N/A |
CRLF injection vulnerability in the HMI web application in Siemens WinCC (TIA Portal) 11 allows remote attackers to inject arbitrary HTTP headers and conduct HTTP response splitting attacks via a crafted URL. | ||||
CVE-2011-4515 | 1 Siemens | 1 Wincc Tia Portal | 2025-04-11 | N/A |
Siemens WinCC (TIA Portal) 11 uses a reversible algorithm for storing HMI web-application passwords in world-readable and world-writable files, which allows local users to obtain sensitive information by leveraging (1) physical access or (2) Sm@rt Server access. | ||||
CVE-2013-0669 | 1 Siemens | 1 Wincc Tia Portal | 2025-04-11 | N/A |
The HMI web application in Siemens WinCC (TIA Portal) 11 allows remote authenticated users to cause a denial of service (daemon crash) via a crafted HTTP request. | ||||
CVE-2013-0668 | 1 Siemens | 1 Wincc Tia Portal | 2025-04-11 | N/A |
Multiple cross-site scripting (XSS) vulnerabilities in the HMI web application in Siemens WinCC (TIA Portal) 11 allow remote attackers to inject arbitrary web script or HTML via a crafted URL. | ||||
CVE-2011-4514 | 1 Siemens | 5 Simatic Hmi Panels, Wincc, Wincc Flexible and 2 more | 2025-04-11 | N/A |
The TELNET daemon in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime does not perform authentication, which makes it easier for remote attackers to obtain access via a TCP session. | ||||
CVE-2013-0667 | 1 Siemens | 1 Wincc Tia Portal | 2025-04-11 | N/A |
Cross-site scripting (XSS) vulnerability in the HMI web application in Siemens WinCC (TIA Portal) 11 allows remote attackers to inject arbitrary web script or HTML via a crafted URL. | ||||
CVE-2013-0659 | 1 Siemens | 4 Cp 1604, Cp 1604 Firmware, Cp 1616 and 1 more | 2025-04-11 | N/A |
The debugging feature on the Siemens CP 1604 and CP 1616 interface cards with firmware before 2.5.2 allows remote attackers to execute arbitrary code via a crafted packet to UDP port 17185. |