Filtered by vendor Siemens Subscriptions
Total 1936 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2016-3155 1 Siemens 1 Apogee Insight 2025-04-12 N/A
Siemens APOGEE Insight uses weak permissions for the application folder, which allows local users to obtain sensitive information or modify data via unspecified vectors.
CVE-2016-2846 1 Siemens 2 Simatic S7 1200 Cpu, Simatic S7 Cpu 1200 Firmware 2025-04-12 N/A
Siemens SIMATIC S7-1200 CPU devices before 4.0 allow remote attackers to bypass a "user program block" protection mechanism via unspecified vectors.
CVE-2016-2200 1 Siemens 15 Simatic S7-1500 Cpu Firmware, Simatic S7-1511-1 Pn Cpu, Simatic S7-1511c-1 Pn Cpu and 12 more 2025-04-12 N/A
Siemens SIMATIC S7-1500 CPU devices before 1.8.3 allow remote attackers to cause a denial of service (STOP mode transition) via crafted packets on TCP port 102.
CVE-2016-2201 1 Siemens 15 Simatic S7-1500 Cpu Firmware, Simatic S7-1511-1 Pn Cpu, Simatic S7-1511c-1 Pn Cpu and 12 more 2025-04-12 N/A
Siemens SIMATIC S7-1500 CPU devices before 1.8.3 allow remote attackers to bypass a replay protection mechanism via packets on TCP port 102.
CVE-2016-1488 1 Siemens 4 Ozw672, Ozw672 Firmware, Ozw772 and 1 more 2025-04-12 N/A
Cross-site scripting (XSS) vulnerability in the login form in the integrated web server on Siemens OZW OZW672 devices before 6.00 and OZW772 devices before 6.00 allows remote attackers to inject arbitrary web script or HTML via a crafted URL.
CVE-2015-7836 1 Siemens 1 Ruggedcom Rugged Operating System 2025-04-12 N/A
Siemens RUGGEDCOM ROS before 4.2.1 allows remote attackers to obtain sensitive information by sniffing the network for VLAN data within the padding section of an Ethernet frame.
CVE-2015-7974 5 Debian, Netapp, Ntp and 2 more 9 Debian Linux, Clustered Data Ontap, Oncommand Balance and 6 more 2025-04-12 7.7 High
NTP 4.x before 4.2.8p6 and 4.3.x before 4.3.90 do not verify peer associations of symmetric keys when authenticating packets, which might allow remote attackers to conduct impersonation attacks via an arbitrary trusted key, aka a "skeleton key."
CVE-2015-8214 1 Siemens 8 Simatic Cp 343-1, Simatic Cp 343-1 Firmware, Simatic Cp 443-1 and 5 more 2025-04-12 N/A
A vulnerability has been identified in SIMATIC NET CP 342-5 (incl. SIPLUS variants) (All versions), SIMATIC NET CP 343-1 Advanced (incl. SIPLUS variants) (All versions < V3.0.44), SIMATIC NET CP 343-1 Lean (incl. SIPLUS variants) (All versions < V3.1.1), SIMATIC NET CP 343-1 Standard (incl. SIPLUS variants) (All versions < V3.1.1), SIMATIC NET CP 443-1 Advanced (incl. SIPLUS variants) (All versions < V3.2.9), SIMATIC NET CP 443-1 Standard (incl. SIPLUS variants) (All versions < V3.2.9), SIMATIC NET CP 443-5 Basic (incl. SIPLUS variants) (All versions), SIMATIC NET CP 443-5 Extended (All versions), TIM 3V-IE / TIM 3V-IE Advanced (incl. SIPLUS NET variants) (All versions < V2.6.0), TIM 3V-IE DNP3 (incl. SIPLUS NET variants) (All versions < V3.1.0), TIM 4R-IE (incl. SIPLUS NET variants) (All versions < V2.6.0), TIM 4R-IE DNP3 (incl. SIPLUS NET variants) (All versions < V3.1.0). The implemented access protection level enforcement of the affected communication processors (CP) could possibly allow unauthenticated users to perform administrative operations on the CPs if network access (port 102/TCP) is available and the CPs' configuration was stored on their corresponding CPUs.
CVE-2015-6675 1 Siemens 1 Ruggedcom Rugged Operating System 2025-04-12 N/A
Siemens RUGGEDCOM ROS 3.8.0 through 4.1.x permanently enables the IP forwarding feature, which allows remote attackers to bypass a VLAN isolation protection mechanism via IP traffic.
CVE-2015-5698 1 Siemens 2 Simatic S7 1200 Cpu, Simatic S7 1200 Cpu Firmware 2025-04-12 N/A
Cross-site request forgery (CSRF) vulnerability in the web server on Siemens SIMATIC S7-1200 CPU devices with firmware before 4.1.3 allows remote attackers to hijack the authentication of unspecified victims via unknown vectors.
CVE-2015-5717 1 Siemens 1 Compas 2025-04-12 N/A
The Siemens COMPAS Mobile application before 1.6 for Android does not properly verify X.509 certificates from SSL servers, which allows man-in-the-middle attackers to spoof servers and obtain sensitive information via a crafted certificate.
CVE-2015-5374 1 Siemens 3 Siprotec 4, Siprotec Compact, Siprotec Firmware 2025-04-12 N/A
A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. Specially crafted packets sent to port 50000/UDP could cause a denial-of-service of the affected device. A manual reboot may be required to recover the service of the device.
CVE-2015-5386 1 Siemens 2 Sicam Mic, Sicam Mic Firmware 2025-04-12 N/A
Siemens SICAM MIC devices with firmware before 2404 allow remote attackers to bypass authentication and obtain administrative access via unspecified HTTP requests.
CVE-2015-5537 1 Siemens 2 Ruggedcom Rox Ii Firmware, Ruggedcom Rugged Operating System 2025-04-12 N/A
The SSL layer of the HTTPS service in Siemens RuggedCom ROS before 4.2.0 and ROX II does not properly implement CBC padding, which makes it easier for man-in-the-middle attackers to obtain cleartext data via a padding-oracle attack, a different vulnerability than CVE-2014-3566.
CVE-2015-5084 1 Siemens 2 Simatic Wincc Sm\@rtclient, Simatic Wincc Sm\@rtclient Lite 2025-04-12 N/A
The Siemens SIMATIC WinCC Sm@rtClient and Sm@rtClient Lite applications before 01.00.01.00 for Android do not properly store passwords, which allows physically proximate attackers to obtain sensitive information via unspecified vectors.
CVE-2015-4174 1 Siemens 1 Climatix Bacnet\/ip 2025-04-12 N/A
Cross-site scripting (XSS) vulnerability in the integrated web server on the Siemens Climatix BACnet/IP communication module with firmware before 10.34 allows remote attackers to inject arbitrary web script or HTML via a crafted URL.
CVE-2015-3610 1 Siemens 1 Homecontrol For Room Automation 2025-04-12 N/A
The Siemens HomeControl for Room Automation application before 2.0.1 for Android does not verify X.509 certificates from SSL servers, which allows man-in-the-middle attackers to spoof servers and obtain sensitive information or modify data via a crafted certificate.
CVE-2015-2822 1 Siemens 1 Wincc 2025-04-12 N/A
Siemens SIMATIC HMI Comfort Panels before WinCC (TIA Portal) 13 SP1 Upd2 and SIMATIC WinCC Runtime Advanced before WinCC (TIA Portal) 13 SP1 Upd2 allow man-in-the-middle attackers to cause a denial of service via crafted packets on TCP port 102.
CVE-2015-2823 1 Siemens 6 Simatic Hmi Basic Panels Generation 1, Simatic Hmi Basic Panels Generation 2, Simatic Hmi Comfort Panels and 3 more 2025-04-12 N/A
Siemens SIMATIC HMI Basic Panels 2nd Generation before WinCC (TIA Portal) 13 SP1 Upd2, SIMATIC HMI Comfort Panels before WinCC (TIA Portal) 13 SP1 Upd2, SIMATIC WinCC Runtime Advanced before WinCC (TIA Portal) 13 SP1 Upd2, SIMATIC WinCC Runtime Professional before WinCC (TIA Portal) 13 SP1 Upd2, SIMATIC HMI Basic Panels 1st Generation (WinCC TIA Portal), SIMATIC HMI Mobile Panel 277 (WinCC TIA Portal), SIMATIC HMI Multi Panels (WinCC TIA Portal), and SIMATIC WinCC 7.x before 7.3 Upd4 allow remote attackers to complete authentication by leveraging knowledge of a password hash without knowledge of the associated password.
CVE-2015-2177 1 Siemens 2 Simatic S7-300 Cpu, Simatic S7-300 Cpu Firmware 2025-04-12 N/A
Siemens SIMATIC S7-300 CPU devices allow remote attackers to cause a denial of service (defect-mode transition) via crafted packets on (1) TCP port 102 or (2) Profibus.