Show plain JSON{"dataType": "CVE_RECORD", "dataVersion": "5.1", "cveMetadata": {"cveId": "CVE-2024-7515", "assignerOrgId": "b73dd486-f505-4403-b634-40b078b177f0", "state": "PUBLISHED", "assignerShortName": "Rockwell", "dateReserved": "2024-08-05T20:19:29.235Z", "datePublished": "2024-08-14T19:40:20.990Z", "dateUpdated": "2024-08-14T19:59:57.056Z"}, "containers": {"cna": {"affected": [{"defaultStatus": "unaffected", "product": "CompactLogix 5380 (5069-L3z)", "vendor": "Rockwell Automation", "versions": [{"status": "affected", "version": "28.011"}]}, {"defaultStatus": "unaffected", "product": "ControlLogix\u00ae 5580 (1756- L8z)", "vendor": "Rockwell Automation", "versions": [{"status": "affected", "version": "28.011"}]}, {"defaultStatus": "unaffected", "product": "GuardLogix 5580 (1756- L8zS)", "vendor": "Rockwell Automation", "versions": [{"status": "affected", "version": "28.011"}]}, {"defaultStatus": "unaffected", "product": "Compact GuardLogix 5380 (5069 \u2013 L3zS2)", "vendor": "Rockwell Automation", "versions": [{"status": "affected", "version": "28.011"}]}, {"defaultStatus": "unaffected", "product": "CompactLogix 5480 (5069-L4)", "vendor": "Rockwell Automation", "versions": [{"status": "affected", "version": "28.011"}]}], "datePublic": "2024-08-13T13:00:00.000Z", "descriptions": [{"lang": "en", "supportingMedia": [{"base64": false, "type": "text/html", "value": "<p><b><u>CVE-2024-7515 IMPACT</u></b></p><p>A denial-of-service vulnerability exists in the affected products. A malformed PTP management packet can cause a major nonrecoverable fault in the controller.</p>"}], "value": "CVE-2024-7515 IMPACT\n\nA denial-of-service vulnerability exists in the affected products. A malformed PTP management packet can cause a major nonrecoverable fault in the controller."}], "impacts": [{"capecId": "CAPEC-153", "descriptions": [{"lang": "en", "value": "CAPEC-153 Input Data Manipulation"}]}], "metrics": [{"cvssV4_0": {"Automatable": "NOT_DEFINED", "Recovery": "NOT_DEFINED", "Safety": "NOT_DEFINED", "attackComplexity": "LOW", "attackRequirements": "NONE", "attackVector": "NETWORK", "baseScore": 8.7, "baseSeverity": "HIGH", "privilegesRequired": "NONE", "providerUrgency": "NOT_DEFINED", "subAvailabilityImpact": "NONE", "subConfidentialityImpact": "NONE", "subIntegrityImpact": "NONE", "userInteraction": "NONE", "valueDensity": "NOT_DEFINED", "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N", "version": "4.0", "vulnAvailabilityImpact": "HIGH", "vulnConfidentialityImpact": "NONE", "vulnIntegrityImpact": "NONE", "vulnerabilityResponseEffort": "NOT_DEFINED"}, "format": "CVSS", "scenarios": [{"lang": "en", "value": "GENERAL"}]}], "problemTypes": [{"descriptions": [{"cweId": "CWE-20", "description": "CWE-20 Improper Input Validation", "lang": "en", "type": "CWE"}]}], "providerMetadata": {"orgId": "b73dd486-f505-4403-b634-40b078b177f0", "shortName": "Rockwell", "dateUpdated": "2024-08-14T19:40:20.990Z"}, "references": [{"url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD%201686.html"}], "solutions": [{"lang": "en", "supportingMedia": [{"base64": false, "type": "text/html", "value": "Upgrade to: \n\n<span style=\"background-color: rgb(255, 255, 255);\">v36.011, v35.013, v34.014</span>"}], "value": "Upgrade to:\u00a0\n\nv36.011, v35.013, v34.014"}], "source": {"discovery": "INTERNAL"}, "title": "Rockwell Automation ControlLogix/GuardLogix 5580 and CompactLogix/Compact GuardLogix\u00ae 5380 Controller Denial-of-Service Vulnerability via Input Validation", "workarounds": [{"lang": "en", "supportingMedia": [{"base64": false, "type": "text/html", "value": "<p>If PTP messages are not used, block at the network level, port UDP 319/320</p>"}], "value": "If PTP messages are not used, block at the network level, port UDP 319/320"}], "x_generator": {"engine": "Vulnogram 0.2.0"}}, "adp": [{"affected": [{"vendor": "rockwellautomation", "product": "compactlogix_5380_firmware", "cpes": ["cpe:2.3:o:rockwellautomation:compactlogix_5380_firmware:v28.011:*:*:*:*:*:*:*"], "defaultStatus": "unknown", "versions": [{"version": "v28.011", "status": "affected"}]}, {"vendor": "rockwellautomation", "product": "controllogix_5580_firmware", "cpes": ["cpe:2.3:o:rockwellautomation:controllogix_5580_firmware:v28.011:*:*:*:*:*:*:*"], "defaultStatus": "unknown", "versions": [{"version": "v28.011", "status": "affected"}]}, {"vendor": "rockwellautomation", "product": "guardlogix_5580_firmware", "cpes": ["cpe:2.3:o:rockwellautomation:guardlogix_5580_firmware:28.011:*:*:*:*:*:*:*"], "defaultStatus": "unknown", "versions": [{"version": "28.011", "status": "affected"}]}, {"vendor": "rockwellautomation", "product": "compact_guardlogix_5380_firmware", "cpes": ["cpe:2.3:o:rockwellautomation:compact_guardlogix_5380_firmware:28.011:*:*:*:*:*:*:*"], "defaultStatus": "unknown", "versions": [{"version": "28.011", "status": "affected"}]}, {"vendor": "rockwellautomation", "product": "compactlogix_5480_firmware", "cpes": ["cpe:2.3:o:rockwellautomation:compactlogix_5480_firmware:28.011:*:*:*:*:*:*:*"], "defaultStatus": "unknown", "versions": [{"version": "28.011", "status": "affected"}]}], "metrics": [{"other": {"type": "ssvc", "content": {"timestamp": "2024-08-14T19:54:17.968076Z", "id": "CVE-2024-7515", "options": [{"Exploitation": "none"}, {"Automatable": "yes"}, {"Technical Impact": "partial"}], "role": "CISA Coordinator", "version": "2.0.3"}}}], "title": "CISA ADP Vulnrichment", "providerMetadata": {"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0", "shortName": "CISA-ADP", "dateUpdated": "2024-08-14T19:59:57.056Z"}}]}}